Home Companies Wuhan GDZX Power Equipment Co., Ltd

Live Test Earth Insulation Tester Double Clamp Ground Resistance Meter,Storage capacity200 groups

Wuhan GDZX Power Equipment Co., Ltd

Contact Us

[China] country

Trade Verify

Address: No.1 Fenghuangyuan Second Road, Jiangxia District, Wuhan City, Hubei Province, China

Contact name:Emma

Inquir Now

Wuhan GDZX Power Equipment Co., Ltd

Verified Suppliers
  • Trust
    Seal
  • Verified
    Supplier
  • Credit
    Check
  • Capability
    Assessment

Live Test Earth Insulation Tester Double Clamp Ground Resistance Meter,Storage capacity200 groups

Country/Region china
City & Province wuhan hubei
Categories Electric Saws
InquireNow

Product Details

                   ZXET3006 Double Clamp Ground Resistance Tester  

 

Good grounding system is an important guarantee of safe and reliable operation of electric power, telecommunications and electrical equipment. The quality of earth resistance is judged by its size. Finding an accurate, fast, simple and reliable method to measure earth resistance has become urgent in lightning protection and grounding field. This Multifunction Dual-Clamp Earth Resistance Tester can be applied to post and telecommunications, power industry, meteorology, equipment room, power distribution wire, tower transmission line, gas station, factory grounding grid, lightning rod and so on.

 

The instrument not only can adopt the traditional auxiliary ground electrode method to measure the earth resistance, but also can measure the earth resistance without auxiliary ground electrode, which change the traditional measurement principle and method of earth resistance: the use of double jaws non-contact measurement technology, without auxiliary ground electrode and isolating grounding body and load, to achieve the on-line measurement. In the single-point earth system and strong interference conditions, it is recommended that using auxiliary ground electrode to measure the resistance

 

Features

 

1. Double clamp / ground piles measurement method: applied to any place to measure whether multi-point or single point grounding.

2. Strong anti-interference ability: Self-generating high-frequency current can filter 50Hz and 100Hz harmonic interference current, even in the 500KV substation environment, it can accurately measure.

3. Wide measurement range and high resolution: Range from 0.01Ω ~ 200Ω, resolution 0.01Ω, the ground resistance under 0.7Ω also can be accurately measured.

4. Large jaw design: Jaw diameter is 50mm (standard configuration), which meets the case using flat iron / steel wire grounding, special jaw size can be customized.

5. High-capacity data storage It can store 200 sets of measurement datum.

6. Simple operation, single-operator Small size, light weight, explosion-proof carrying case, easy for field measurements.

 

Technical parameters:

 

Measurement rangeDouble clamp method0.01Ω~200Ω
Ground piles method0.01Ω~200Ω
ErrorDouble clamp method±3%±2 digits
Ground piles method±2%±2 digits
Minimum resolution0.01Ω
Jaw sizeΦ50mm
Storage capacity200 groups
Temperature0℃~+50℃
Power supply8 AA NiMH rechargeable batteries or regular AA batteries
Weight0.8KG (battery included)
Dimension265×130×65mm3

 

 

Hot Products

Product Description This series devices are designed for AC withstand voltage test of substation ...
Inductance Adjustable AC Voltage Withstand Resonant Test System for Generators High Voltage Test ...
ZXBXZ Series Resonant Test System for Substation Product introduction This ZXBXZ Series Devices are ...
ZXBXZ Series Resonant Test System for Substation Product introduction This ZXBXZ Series Devices are ...
Resonant test system for CVT This resonant tester is widely used for Capacitive Voltage Transformer ...
High Voltage Resonant Test System Inductance Adjustable AC High Voltage Resonant Test System For ...