Home Companies herong electric

High Voltage Pole Mounted Load Break Switch 12KV 24KV 33KV 4001A 600A 1250A

herong electric

Contact Us

[China] country

Trade Verify

Address: NO.9 XIJIN RD, JINGWEI INDUSTRIAL PARK, ECONOMIC AND TECHNOLOGY DEVELOPMENT ZONE, XI'AN CITY, SHAANXI PROVINCE, CHINA

Contact name:Amanda

Inquir Now

herong electric

Verified Suppliers
  • Trust
    Seal
  • Verified
    Supplier
  • Credit
    Check
  • Capability
    Assessment

High Voltage Pole Mounted Load Break Switch 12KV 24KV 33KV 4001A 600A 1250A

Country/Region china
City & Province Shaanxi
Categories Battery Chargers
InquireNow

Product Details

GW1A-12KV/24KV/33KV-4001/600A/1250A Outdoor Pole Mounted Disconnector

 

 

1 ,Product overview
1.1 Application
GW1A type outdoor AC high voltage isolation switch is AC 50Hz/60Hz outdoor device, is used in below 33 kv the supply network, for high voltage line and under the situation with voltage, as well as on the maintenance of high voltage bus, circuit breakers and other electrical equipment with high voltage line charged electrical isolation. But also switch small capacitance current and inductive current.
This product is divided into regular and anti-pollution type two kinds.
CJ6 Motor or CS8-5 rainproof type manual.
This product can be with Arc Extinction Horn or Chamber
This product can be with Conductor in Cable or Soft Busbar
This product cab be with Fuse or without Fuse


1.2 Environmental

  1. Altitude≤2000m,more higher ,should be redesigning by sea level
  2. Ambient air temperature:-40≤T≤ +50ºC;
  3. Wind pressure ≤700Pa;
  4. Seismic intensity ≤8 degree;
  5. Radial thickness of ice≤10mm;

 

2 ,Main technical parameters Pic 1

Technical sheet

 

Item
GW2-12WGW1-24WGW1-38W
Ur kV102033
Volts RMS kV122438
Rated insulation level1Min power frequency withstand voltage kV(RMS)to earth405070
Fracture476080
lightning impulse withstand voltage kV(peak value)to earth105125170
Fracture120145195
Rated frequency Hz50/60
Rated current A200,400,630,1250
The thermal stability of current 4 seconds kA(RMS)6.3,12.5,20,31.5
Dynamic current kA(peak value)16,31.5,50,80
operating mechanismCJ6 Motor or CS8-5 rainproof type manual
With Fuse50A,100A,200A OR NONE
ConductorCABLE OR SOLF BUSBAR

 

 

3, Construction
This disconnector(Size as shown in figure 1)is the three-phase on one chassis knife switch, or made up of three single phase.As shown, can be divided into the chassis, insulator and conductive parts, chassis by the rotor and the bending of plate and Angle steel welded frame, chassis fixed six porcelain insulator, and every two composition, mounted on the rotating shaft three-phase insulator to operate, and close movement used to operating three-phase knife, conductive part is composed of contactor, knife and contact, with the spring pressure.
Break-brake in turn by the operating arm shaft rotates, operating insulator up divide the knife and contact with the knife, knife touch the revolving around, contact also in knife leads up to the gate location.
Turn by the operating arm shaft rotates when closing, turns operating insulator with the knife, in and after contact to meet contact rotates, together go to closing position.

Hot Products

High Voltage 6.6kv Capacitor Shunt Type With Capacity 25kVar 1. Overview of High Voltage 6.6KV ...
High Voltage Shunt Power Capacitor BAM6.6-50-1W, High Voltage Capacitor Main features of High ...
High Voltage Shunt Power Capacitor BAM6.6-100-1W, High Voltage Capacitor Function of High Voltage ...
High Voltage Shunt Power Capacitor BAM7.96-25-1W, High Voltage Capacitor 1. Overview of High Voltage ...
High Voltage 7.96kv Capacitor Shunt Type With Capacity 50kVar 1. Overview of High Voltage 7.96KV ...
High Voltage 9.1kv Capacitor Shunt Type With Capacity 150kVar 1. Overview of High Voltage9.1KV ...