Home Companies Xi'an Kacise Optronics Co.,Ltd.

Ultrasonic Sensor for Distance and Level Measurement of KUS630

Xi'an Kacise Optronics Co.,Ltd.

Contact Us

[China] country

Trade Verify

Address: i City, No11, TangYan South road, Yanta District, Xi'an,Shaanxi,China.

Contact name:Evelyn Wang

Inquir Now

Xi'an Kacise Optronics Co.,Ltd.

Verified Suppliers
  • Trust
    Seal
  • Verified
    Supplier
  • Credit
    Check
  • Capability
    Assessment

Ultrasonic Sensor for Distance and Level Measurement of KUS630

Country/Region china
City & Province Shaanxi
InquireNow

Product Details

 

KUS630 Series Ultrasonic Level Meter

 

1.Features

  • High sensitivity.
  • Fully sealed
  • IP68 protection class
  • Corrosion-resistant housing, suitable for corrosive media and applications

2. Dimensions

Unit in the diagram is mm.

3. Electrical connections and signal definitions

Line orderColourDefinition
1RedPower is positive
2Blackpower return ground
3YellowAnalog output, voltage output, current output switch output
4BlueRS485 A+ or uart TXD
5GreenRS485 B- or uart RXD

 

Cable colorLine orderDescribeRemark
red1powered by3.3V-30V wide voltage input
black2GND 
yellow3Switch outputSwitch terminal, load capacity 1A 60V, supports up to two switch outputs with independent logic, the two terminals are the two contacts of the switch, do not distinguish between positive and negative poles, and can be connected at will.
White4Switch output
brown4RS485A+ 
green5RS485B- 

 

 

4.Parameter description

 

 

Working current

≤ 45 mA (fastest measurement speed)

Low-power version, sleep power consumption is less than 0.3mA, sending power consumption is 20mA (less than 2ms), and receiving power consumption is not more than 8mA (less than 150ms)

 

 

Output signal

1:Programmable analog output 0-10V.

2:RS485 output.

3:Uart serial output

4:4-20mA output

5:Switch output

Measurement accuracy≤1 %
Temperature compensationyes

 

    working conditions

 

Working temperature-25…70℃(248...343K)
Storage temperature-40…85℃(233...358K)

 

other instructions

 

Electrical connection5-core cable (analog output), 6-core cable (switch output);
Protection classIP68
Shell materialPVC /PVDF/PTFE/ABS

 

5. Sensor function

analog

The analog output can be set through RS485, and the sensor can work in 8 modes. The specific reference is as follows:

Step 1: Connect to the host computer through serial port debugging assistant or modus debugging assistant.

Step 2, set a near point reference distance point.

Step 3, Set a far point reference point

Step 4, set the output voltage or current of the near-point reference point.

Step 5, set the output voltage or current of the far point reference point.

Step 6, set the analog output to switch characteristic selection.

Step 7, set the analog output as linear output or switch output option.

Step 8, reset the sensor to make the new parameters take effect.

8 working modes of the sensor.

1: Open window mode by default

2: Windowed mode is turned off by default

3: Single-point mode is turned on by default

4: Single-point mode is turned off by default

5: Single-point hysteresis mode is turned on by default

6: The single-point hysteresis mode is turned off by default

7: The presence or absence of detection mode is turned on by default

8: The presence or absence of detection mode is turned off by default

 

485 output data

485 output data is in MODBUS-RTU format. Refer to the software instruction manual for details.

 

 

 

6.Serial port setting output form example


7. Ordering Information

 

 

 

KUSModelOutputRangeDescribe
 630AProduct series model and shape, the default delivery is TypeA, support customization
630B
630C
Custommade
 0-10VAnalog 0-10V output
0-5VAnalog 0-5V output
0-3VAnalog 0-3V output
4-20mAAnalog 4-20mA output
SWSwitch output
UartUart serial output MODBUS RTU protocol
RS485RS485 output MODBUS RTU protocol
 XXX mm

XXX mmmeans the maximum measurement distance

(default1000mm)

KUS550RS48510000mm 

 

 

 

 
 
 
 
 
 
 
 
 
 
 
 
 


 

Hot Products

1. Description KPS110 pressure and temperature integrated transmitter is a temperature and pressure ...
Kacise IP66 High Accuracy Wide Pressure Range Digital Pressure Gauge With Data Logger 1. Features 1) ...
Kacise IP66 High Accuracy Wide Pressure Range Digital Pressure Gauge With Data Logger 1. Overview ...
Kacise IP66 High Accuracy Wide Pressure Range Digital Pressure Gauge With Data Logger 1. Overview ...
Kacise IP66 High Accuracy Wide Pressure Range Digital Pressure Gauge With Data Logger 1. Overview ...
Kacise IP66 High Accuracy Wide Pressure Range Digital Pressure Gauge With Data Logger 1. Overview ...