Techsafe Materials Suzhou co.,ltd |
|
More details,pls visit www.labppe.com
SH755B1-Portable/bench eye wash,brass
Item no.:SH755B1
Product name:Portable/bench eye wash,brass
Fixing:fixing in table or wall
Material:brass
Sprayer head:has dust shield cap,can be removed when eye wash operated
Function:on the basis of the water pressure, the valve for flow control can
be adjusted in order to adapt for the eyes
Switch:automatic trigger locking for easy hand-free use
Pipe length:1.4m, PVC with stainless steel net
Pressure:Max. 7Bar
Emergency shower,Eyewash,eye wash,Eye wash stations,eye washing,safety showers,eye wash solution,bradley eye wash,Emergency eye wash station,Emergency safety shower,Eye safety,eye washer,
Personal Protective Equipment:Emergency shower & Safety eye wash,Drench shower,Safety shower,Face wash bath,Eyewash station,Emergency shower.OSHA,ANSI Z358.1-2004,CE certificate.ISO9001:2008.
Head |
Installed so the fluid flow pattern is no less than 33 inches but no greater than 53 inches from the work surface |
Positioned 6 inches from wall or nearest obstruction |
Deliver 0.4 GPM tepid flushing fluid for 15 minutes at 30 psi for plumbed units |
Deliver 0.4 GPM tepid flushing fluid for 15 minutes for gravity-fed units |
Head & Flushing fluid units must be protected from airborne contaminants & the removal of any protective device(s) must not require a separate motion by the user |
Valves |
Activate in one second or less |
Stay open valve |
Valve remains on until the user shuts it off |
Emergency Shower Heads |
Positioned 82 to 96 inches in height from the work surface |
Spray pattern will have a minimum diameter of 20 inches at 60 inches above the work surface |
Must deliver tepid flushing fluid |
Flow rate equal to 20 gallons per minute (GPM) for a minimum of 15 minutes at 30 pounds per square inch (PSI) (Plumbed Units Only) |
Flow rate equal to 20 GPM for a minimum of 15 minutes (self contained units only) |
The center of the spray pattern must be located at least 16 inches from any obstruction |
Valves |
Activate in one second or less |
Stay open valve |
Valve remains on until the user shuts it off |
Manufacture product catalogs with requested information should be supplied |
Manufacture authorization of the bidder to represent the given brand |