Home Companies Delta Technology (Chongqing) Co., Ltd.

PRT-PC3 High Speed Electrical Relay Protection Tester

Delta Technology (Chongqing) Co., Ltd.

Contact Us

[China] country

Trade Verify

Address: No.85 Zhong Shan Yi Road, Yu Zhong District, Chongqing, China. 400010

Contact name:Tina Chen

Inquir Now

Delta Technology (Chongqing) Co., Ltd.

Verified Suppliers
  • Trust
    Seal
  • Verified
    Supplier
  • Credit
    Check
  • Capability
    Assessment

PRT-PC3 High Speed Electrical Relay Protection Tester

Country/Region china
City & Province chongqing chongqing
Categories Battery Chargers
InquireNow

Product Details

PRT-PC3 High Speed Electrical Relay Protection Tester

Introduction:

  • PRT-PC3 High Speed Electrical Relay Protection Tester  is applied to test the relay unit in relay protection system.
  • At the same time PRT-PC3 High Speed Electrical Relay Protection Tester could be considered as a universal three phase AC/DC voltage source or current source.
  • PRT-PC3 High Speed Electrical Relay Protection Tester is applied to test protection replay based on voltage and current operation.
  • The main function of PRT-PC3 High Speed Electrical Relay Protection Tester include: calibration of voltage and current operation relays, secondary circuit inspection,trip value of circuit breaker test, switch on and off time measurement of circuit breaker and so on.
  • PRT-PC3 High Speed Electrical Relay Protection Tester is a low cost, simple operation and reliable performance device for secondary circuit test.

 

 

Parameters:

No.

Items

Specifications

Alternating Current(AC) output

1

Output accuracy

0.5magnitude

2

Phase current output (effective value)

0~30A

3

Three parallel phase current output (effective value)

0~90A

4

Phase current value with long time under permission (effective value)

10A

5

Phase current maximum power output

420VA

6

Three parallel phase current maximum power output

900VA

7

Three parallel phase current maximum work time

10s

8

Frequency range (base wave)

20~1000Hz

9

Harmonic frequency number

1~20 time

Direct Current(DC) output

1

Output accuracy

0.5magnitude

2

Current output

0 ~ ± 10 A/each phase

0 ~ ± 30 A/every three parallel

3

Maximum output of load voltage

20v

Alternating Voltage output

1

Output accuracy

0.5magnitude

2

Phase voltage output (RMS)

0 ~ 120v

3

Line voltage output (RMS)

0 ~ 240v

4

Phase voltage/line voltage power output

80VA/100VA

5

Frequency range (base wave)

20 ~ 1000Hz

6

Harmonic frequency number

1 ~ 20 times

Direct voltage output

1

Output accuracy

0.5magnitude

2

Phase voltage output amplitude

0 ~ +160v

3

Line voltage output amplitude

0 ~ + 320v

4

Phase voltage/line voltage power output

70VA/140VA

 

1

AC current and voltage error

<0.5%RDG+0.05%FS

2

DC current error

<0.5%RDG+0.05%FS

3

DC voltage error

1%RDG+0.1%FS

4

Binary input

Active node 0~250V, 0~6V for “0”, 6~250V for “1”, passive node: 20mA max

5

Binary output

DC 220V/0.2A, AC 220V/0.5A

The switch quantity and time measurement

1

Switch parameters input

7 ways; Empty contact: 1~20mA, 24v;

Power contact access: “0”:0~+6V;

“1”:+11 V~+250V;

2

Switch parameters output

2 couples DC: 220V/0.2A; AC: 220V/0.5A

3

Time measurement

Measuring range: 0.1ms ~ 9999s / 0.1ms

 

1

Power supply

AC220V ± 10%, 50Hz/60Hz

2

Environment temperature

0~50°C

3

Humidity

≤85%RH

4

Weight

<18KG

 

 

PRT-PC3 High Speed Electrical Relay Protection Tester Real Picture:

 

Hot Products

CBA-III Circuit Breaker Timer Dynamic Resistance Meter Contact Resistance Tester Introduction: CBA...
SR-601 12 Channels Curve Data Logger Data Recorder for Power System Introduction: SR-601 Data Logger ...
SR-601 Generator Motor Waveform Curve Testing Digital Signal Recorder Introduction: SR-601 Signal ...
SR-601 Instantaneous Power Signal Recorder Power Data Logger Introduction: SR-601 Signal Recorder is ...
XDC-2 Handheld Lead Acid Battery Internal Resistance Tester Introduction: XDC-2 Handheld Lead Acid ...
XDC-2 Digital Battery Conductance Testing Battery Internal Resistance Meter Introduction: XDC-2 ...