Home Companies Qingdao Hengfengyou Electrical Engineering Co., Ltd.

pre-assembled power distribution package Substation,European style hot model

Qingdao Hengfengyou Electrical Engineering Co., Ltd.
Active Member

Contact Us

[China] country

Address: N0.506 Huicheng Road, Chengyang District, Qingdao City,China

Contact name:Jack

Inquir Now

Qingdao Hengfengyou Electrical Engineering Co., Ltd.

pre-assembled power distribution package Substation,European style hot model

Country/Region china
City & Province qingdao shandong
Categories Other Chargers
InquireNow

Product Details

Prefabricated Electrical Substation Box 4000A Rated Current For Power   Distribution
 
    
                                     
 
Overview

Hengfengyou offer an environmentally responsible, high efficiency, safer choice. The units have high-fire-point fluid, providing fire safety benefits, and a projected life well beyond that of a traditional mineral-oil transformer. These efficient and cost-effective transformers use Environmental friendly oil. Envirotran transformers are manufactured in 50 - 10,000kVA, in primary voltage classes of 11kV,15 kV, 25 kV and 35 kV.
 
capacity kVA 50-20,000
 
Primary Voltage Up to 34,500 V
 
Secondary Voltage 208-14,400 V
 
Application
Three-phase, pad-mounted transformers, for use on underground power distribution systems, are best suited for commercial applications in public access areas and where underground service is required. These transformers meet modern design requirements for flexibility and provide a visually pleasing installation. Construction allows installation in locations accessible to the general public without the need for protective fencing or vaults. These units are ideally suited for apartment buildings, schools, hospitals, shopping centers, commercial buildings, or industrial sites.
 
Service condition
 
-Sealed tank construction
-Special waste disposal considerations
-Insulation temperature limit: 120 °C
-Temperature rise: 65 °C (standard); 55 °C or 55/65 °C (optional)
 
Special Design Options
 
-Special sound requirements
-Special altitude requirements
-Retrofit designs
-Highe efficiency requirements
-Special ambient conditions
 
Applicable Standards
 
-IEEE C57.12.00—Standard General Requirements for Liquid-Immersed Distribution, Power, and Regulating Transformers
-IEEE C57.12.34—Requirements for Pad-Mounted, Compartmental-Type, Self-Cooled, Three-Phase Distribution Transformers, 2,500 kVA and Smaller: High Voltage, 34,500 GrdY/ 19,920 V and Below; Low Voltage, 480 V and Below

                                     
Parameters

Rated
power
(KVA)
High
Voltage
(KV)
H.VTap
range
Low
Voltage
(kV)
Connection
Symbol
Short-Circuit
Impedance
(%)
No-load
Loss
(W)
On-Load
LoSS
(W)
No-load
Current
(%6)
Insulation
Class
SC(B)
9
SC(B)
10
SC
(B)
SC
(B)
10
306
6.3
10
10.5
11
+5%
OR
+2x2.5%
0.4Yyn0
Dyn11
42201907507102.3F
50310270106010002.2
80420370146013801.7
100450400167015701.7
125530470196018501.5
160610540|225021301.5
200700620268025301.3
250810720292027601.3
315990880367034701.1
4001100980422039901.1
50013101160|5170|48801.1
63015101340622058800.9
630614601300|631059600.9
80017101520|736069600.9
100019901770861081300.9
1250235020901026096900.9
16002760245012400117300.9
20003400305015300144500.7
25004000360018180171700.7

 
 
 
 
 

 
Product composition

NITIZED SUB STATION CONFIGURATION COMPONENTS
 
HV Compartment
Extendible & Non Extensible MV Switchgear – Ring Main Unit (RMU)
Vacuum / SF6 Circuit Breaker, RMU & HV Fuse.
RMU & Load Break Switch.
Protection & Metering Devices.
Current & Potential Transformer for Metering / Protection.
 
Transformer Compartment
Oil Immersed Transformer /
Dry Type Transformer (VPI)
 
LV Compartment
LV Distribution Board
LT Control Panel with Incomer ACB & Outgoing MCCB
APFC Panel
LV Switch fuse unit
Instrumentation and Metering
 
Illumination
Internal Lightning & Door Limit Switches, Tailor made enclosures mounted on the transformer under base to provide single lift complete
installation with theft proof design.
 
 
Applications
USS (Unitized Sub Stations) / Package Sub Station are ideally suited for new residential and commercial complexes as it can be placed on Ground, partially or totally below / above ground level. Mainly used by Power Utilities, Multiplexes, Hotels, Hospitals, Shopping Malls, Software Parks, Residential Complex, Airport etc.


 
Service Centre
 
The shell of the box is made of aluminum-coated zinc steel plate and container manufacturing  technology, and the design is beautiful. On the premise of ensuring the reliability of power supply, the shell color of the box-type substation is selected, so that it is easy to be in harmony with the surrounding environment Especially suitable for urban construction.
 
Such as: Urban residential  areas, stations, ports, airports, parks, green belt and other densely populated areas, it can be  used as a fixed substation, can also be used as a mobile substation, with decorative and  beautifying the environment.
 

 
 
 

Hot Products

Dry type transformer Product introduction Scb10 epoxy resin cast dry-type transformer is an upgrade ...
Dry type transformer Product introduction Scb11 epoxy resin cast dry-type transformer is safe, flame...
Scb12-315kVA Dry Type Transformer Scb12 Dry Type Power All Copper Transformer Manufacturer Direct ...
Dry type transformer Product introduction Compared with model scb12 epoxy resin cast three-phase dry...
Dry type transformer Product introduction SCB10 / 11 series non-encapsulated dry-type transformer ...
Dyn11 Yyn 06~10kv 30-2500kVA 3 Phase Dry Type Power Frequency Distribution Transformer SCB Dry Type ...