ELECMAN ® 1-5/8" * 13/16"(41*21mm) Galvanized Steel Strut Channel ES-510

 

Applications

 

ELECMAN® 1-5/8" * 13/16"(41*21mm) galvanized steel strut channel ES-510 are designed for structural applications, strut channels are typically used for the suspension of pipes, ducts, and equipment. They can be interconnected and secured using strut nuts.

 

Features

 

The main advantage of strut channel in construction is that there are many options available for rapidly and easily connecting lengths together and other items to the strut channel, using various specialized strut-specific fasteners and bolts.It can be assembled very rapidly with minimal tools and only moderately trained labor, which reduces costs significantly in many applications.A strut channel installation also can often be modified or added-to relatively easily if needed.

 

 

Specification Data

 

ELECMAN provides full size 1-5/8" * 13/16"(41*21mm) galvanized steel strut channel ES-510.

 

Section Properties1-1 AXIS2-2 AXIS
Cat.#WT/FTAREAIxSxRxIySyRy
LBS.SQ.IN.in⁴in³inin⁴in³in
ES-5100.810.2410.0220.0640.3020.0910.1120.614

 

 

Allowable Beam Loads - Span In Inches
Cat.#STRESS24"30"36"42"48"60"72"84"96"108"120"
ES-5101/2403903102602251951551301101009080
37023516512090604030252015
1.TOTAL STATIC LOAD in LBS.
2.Upper line is MAXIMUM ALLOWABLE UNIFORM LOAD creating 25000 PSI Bending Stress about the X-Axis based on SIMPLE BEAM condition.
3.Lower line shows TOTAL UNIFORM LOAD which produces a deflection of 1/240th of the SPAN(i.e.: ½. Def. for 120" Span )
4.Multiply values in upper line by 0.5 to obtain ALLOWABLE CENTER CONCENTRATED LOAD at 25000 PSI Stress. Deflection by 0.8.
5.* Load limited by spot weld shear.
6.For punched channel, reduce weld limited loads by 0.75 due to 4" weld spacing.
7.*** Load controlled by 25,000 PSI design stress.

 

Allowable Column Loads - Unsupported Height of Column in Inches
Cat.#24"30"36"42"48"60"72"84"96"108"120"
ES-510389034703070257021001350940************

1. COLUMN LOADS are allowable axial loads applied at the section centroid. Loads applied at the slot face must be reduced for eccentricity.

2. ALLOWABLE COLUMN LOADS shown are based upon an effective length factor K=0.8 standard engineering practice required for evaluation of other conditions.

 

 

Packing Information

 

Packing is so important, good packing can help customers to improve the brand image, good packing also can help customers to stock the products well for a longer time. ELECMAN® Strut channels are usually packed in bundles, small bundles or big bundles are both available. ELECMAN can follow any packing requirements of customers.

 

 

Hot Products

ELECMAN ® UL797 ANSI 80.3 Electrical Metallic Tubing (EMT Conduit) EMT Pipe Application ELECMAN® ...
ELECMAN ® 1/2 in. UL797 Hot Dipped Galvanized Electrical Metallic Tubing EMT Conduit Application ...
ELECMAN ® ANSI 80.3 UL797 3/4 Inch Electrical Metallic Tubing EMT Conduit Application ELECMAN® ANSI ...
ELECMAN ® 1" UL797 GI Electrical Metallic Tubing EMT Conduit EMT Pipe EMT Tube Application ELECMAN® ...
ELECMAN ® UL797 Electrical Metallic Tubing EMT Electrical Cable Conduit 1-1/4 In. Application ...
ELECMAN ® 1-1/2" ANSI 80.3 UL797 Thin Wall Electrical Metallic Tubing EMT Conduit Application ...