Home Companies Guangdong EuroKlimat Air-Conditioning & Refrigeration Co., Ltd

R407C Screw Air Cooled Heat Recovery Unit With Spiral Axial Fan 85 - 470 Tons

Guangdong EuroKlimat Air-Conditioning & Refrigeration Co., Ltd
Active Member

Contact Us

[China] country

Address: Euroklimat Industrial Park, Huangjiang Dongguan Guangdong China 523766

Contact name:LENG Zhengliang

Inquir Now

Guangdong EuroKlimat Air-Conditioning & Refrigeration Co., Ltd

R407C Screw Air Cooled Heat Recovery Unit With Spiral Axial Fan 85 - 470 Tons

Country/Region china
City & Province dongguan guangdong
InquireNow

Product Details

 

 

R407C Screw type air cooled (heat pump) partial heat recovery unit 85 - 470 tons

 

 

Specifications

 

 

Model 

EKAS

085

EKAS

095

EKAS

115

EKAS

125

EKAS

140

EKAS

150

EKAS

165

EKAS

180

Nominal cooling capacitykW284.1328.3388.0410.3473.7509.4557.3601.0
USRT80.893.3110.3116.7134.7144.8158.5170.9
×104kcal/h24.428.233.435.340.743.847.951.7
Nominal heating capacity*kW322.7354.7426.9431.3491.6528.6578.4623.7
USRT91.8100.9121.4122.6139.8150.3164.4177.3
×104kcal/h27.830.536.737.142.345.549.753.6
Partial heat recovery capacitykW71.082.197.0102.6118.4127.3139.3150.2
×104kcal/h6.17.18.38.810.211.012.012.9
Cooling compressor powerkW93.1101.3123.9128.6146.1157.0171.4182.0
Heating compressor powerkW95.8104.1124.1135.1153.4164.8179.9189.6
Capacity modulation 25% ~ 100% stepless modulation
Startup type Y-Δ
Power supply 380V/3~/50Hz
RefrigerantType R407C
Circuit Qty. 11111111
Control mode Electronic expansion valve
CompressorType Semi-closed double screw type
Qty. 11111111
LubricantCode EK02
Filling quantity 13x113x113x113x119x119x123x123x1
FanType Spiral axial fan
Qty.No.688810101212
CapacitykW10.814.414.414.418.018.021.621.6
Air flow×104m3/h1216161620202424
Air side heat exchangerType Fins
Densitypiece/inch16FPI
Water side heat exchangerType Dry shell-tube type
Water flow for coolingm3/h48.956.566.770.681.587.695.9103.4
Pressure drop of cooling waterkPa5862736466615156
Water flow for heating*m3/h55.561.073.474.284.690.999.5107.3
Pipe diameterinch45555888
Heat exchanger at the heat
recovery side
Type Plate heat exchanger
Water flowm3/h12.214.116.717.620.421.924.025.8
Pipe diameterinch22222222
Rated currentA185207246254292311344362
Startup currentA250278326338388413455480
Max. startup currentA357357478478660660749749
DimensionsLengthmm32004100410041005000500059005900
Widthmm22602260226022602260226022602260
Heightmm25252525252525252525252525252525
Weight of a single indoor unitShipment of cooling only unitskg38654015416547654810481053805500
Operation of cooling only unitskg40154165431549154966496655405660
Shipment of heat pump unitskg39504100425048504900490054805600
Operation of heat pump unitskg41004250440050005056505656405760

 

 

Model 

EKAS

190

EKAS

200

EKAS

210

EKAS

225

EKAS

235

EKAS

250

EKAS

275

EKAS

300

Nominal cooling capacitykW636.4683.3728.2797.2819.9820.6919.71018.7
USRT181.0194.3207.1226.7233.1233.3261.5289.7
×104kcal/h54.758.862.668.670.570.679.187.6
Nominal heating capacity*kW660.5709.1749.9813.3838.6862.7959.91057.2
USRT187.8201.6213.2231.2238.4245.3272.9300.6
×104kcal/h56.861.064.569.972.174.282.690.9
Partial heat recovery capacitykW159.1170.8182.1199.3205.0205.2229.9254.7
×104kcal/h13.714.715.717.117.617.619.821.9
Cooling compressor powerkW192.8206.9207.8221.3227.4257.2285.6314.1
Heating compressor powerkW200.8215.1214.2226.6232.4270.2299.9329.6
Capacity modulation 25% ~ 100% stepless modulation12.5%~100% stepless modulation
Startup type Y-Δ
Power supply 380V/3~/50Hz
RefrigerantType R407C
Circuit Qty. 11111222
Control mode Electronic expansion valve
CompressorType Semi-closed double screw type
Qty. 11111222
LubricantCode EK02
Filling quantity 23x123x123x123x123x113x219+1319x2
FanType Spiral axial fan
Qty.No.1214141616161820
CapacitykW21.625.225.228.828.828.832.436.0
Air flow×104m3/h2428283232323640
Air side heat exchangerType Fins
Densitypiece/inch16FPI
Water side heat exchangerType Dry shell-tube type
Water flow for coolingm3/h109.5117.5125.3137.1141.0141.2158.2175.2
Pressure drop of cooling waterkPa4351567344455364
Water flow for heating*m3/h113.6122.0129.0139.9144.2148.4165.1181.8
Pipe diameterinch88888888
Heat exchanger at the heat
recovery side
Type Plate heat exchanger
Water flowm3/h27.429.431.334.335.335.339.543.8
Pipe diameterinch22222222
Rated currentA381413415446457508565622
Startup currentA505548549590594676751826
Max. startup currentA882882882882882732931931
DimensionsLengthmm59006800680077007700810090009900
Widthmm22602260226022602260226022602260
Heightmm25252525252525252525252525252525
Weight of a single indoor unitShipment of cooling only unitskg55205555575558055835958096759670
Operation of cooling only unitskg56805715593559856015988099879982
Shipment of heat pump unitskg56205670587059205950975098509850
Operation of heat pump unitskg57805830605061006130100501016210162

 

 

Model EKAS330EKAS360EKAS380EKAS400EKAS420EKAS445EKAS470
Nominal cooling capacitykW1110.31201.91284.31366.61456.41548.11639.7
USRT315.7341.7365.2388.6414.1440.2466.2
×104kcal/h95.5103.4110.4117.5125.3133.1141.0
Nominal heating capacity*kW1152.21247.31332.71418.21499.81588.51677.3
USRT327.6354.6378.9403.2426.4451.7476.9
×104kcal/h99.1107.3114.6122.0129.0136.6144.2
Partial heat recovery capacitykW277.6300.5321.1341.6364.1387.0409.9
×104kcal/h23.925.827.629.431.333.335.3
Cooling compressor powerkW339.0364.0388.9413.8415.6435.2454.8
Heating compressor powerkW354.4379.2404.7430.3428.4446.6464.9
Capacity modulation 12.5%~100% stepless modulation
Startup type Y-Δ
Power supply 380V/3~/50Hz
RefrigerantType R407C
Circuit Qty. 2222222
Control mode Electronic expansion valve
CompressorType Semi-closed double screw type
Qty. 2222222
LubricantCode EK02
Filling quantity 23x223x223x223x223x223x223x2
FanType Spiral axial fan
Qty.No.22242628283032
CapacitykW39.643.246.850.450.454.057.6
Air flow×104m3/h44485256566064
Air side heat exchangerType Fins
Densitypiece/inch16FPI
Water side heat exchangerType Dry shell-tube type
Water flow for coolingm3/h191.0206.7220.9235.1250.5266.3282.0
Pressure drop of cooling waterkPa47546475844854
Water flow for heating*m3/h198.2214.5229.2243.9258.0273.2288.5
Pipe diameterinch8888888
Heat exchanger at the heat
recovery side
Type Plate heat exchanger
Water flowm3/h47.751.755.258.862.666.670.5
Pipe diameterinch2222222
Rated currentA673724775826829871913
Startup currentA89396010281096109811531188
Max. startup currentA1063106312151239124112411275
DimensionsLengthmm10800117001260013500135001440015300
Widthmm2260226022602260226022602260
Heightmm2525252525252525252525252525
Weight of a single indoor unitShipment of cooling only unitskg10820110601107511160115601166011720
Operation of cooling only unitskg11140113801139511480119201202012080
Shipment of heat pump unitskg11010112501129011390117901189011950
Operation of heat pump unitskg11330115701161011710121501225012310

 

Note:
■ Rated cooling work conditions: outdoor dry bulb: 35°C; outlet water temperature: 7°C; water flow 0.172m3/(h·kW).
■ Rated heating work conditions: outdoor dry/wet bulb: 7°C/6°C; outlet water temperature: 45°C; water flow 0.172m3/(h·kW).
■ Rated working conditions for partial heat recovery units: inlet/outlet hot water temperature 50°C/55°C; inlet/outlet temperature of chilled
water: 12°C/7°C; ambient dry bulb temperature 35°C.
■ *Heating parameters marked with only apply to heat pumps units. Cooling only EKAS units do not have these parameters.
■ For on-site electric wiring, see the name plate or installation menu of the unit.

 

Inheriting the supreme air cooling design from EK Italy and equipped with the leading-edge total heat recovery technology, environment friendly units of R407C series can provide hot water with a temperature as high as 65°C to meet the air conditioning and hot water requirements of hospitals, clubs, factories, and so on.

 

More Energy Saving

 

The heat recovery technology improves cooling efficiency, reduces power consumption, and extends the service life of a unit. The total heat recovery technology recovers all condensate heat, saves power consumed by the fan of the heat exchanger at the air side, and reduces energy consumption by more than 15%.

 

One Unit for Three Purposes

 

One unit can be used for three purposes: cooling, heating, and free hot water. The unit can provide hot water with a temperature up to 65°C to meet guest house showering, kitchen cleaning, and factory hot water consumption requirements, thus saving investment in hot water equipment.

 

Less CO2 and More Environment Friendly

 

EK air conditioners feature a leading-edge total heat recovery technology to use waste heat, greatly save energy, and effectively mitigate the heat island effect in cities due to waste heat dissipation.

 

Easy Installation

 

The unit can be easily installed outside and requires no dedicated equipment room or operator. Free hot water is available as long as you connect the hot water pipes.

Hot Products

68kW R410A Refrigerant Air Cooled Modular Chiller with DANFOSS Compressor Specifications: EKAC ...
R410a air cooled modular chiller 68KW/90KW/95KW/100KW/134KW/150KW Specifications: Basic Model ...
Features 1. Copeland scroll compressor or Danfoss scroll compressor 2. Plate heat exchanger or shell ...
Totally Heat Recovery Air Cooled Modular Chiller 130KW Features 1. Copeland scroll compressor or ...
Tropical area air cooled scroll chiller max working ambient temperature 56 C Features 1. 4 nos ...
EVI air cooled scroll chiller Features 1. 4 nos Copeland scroll compressors 2. Plate heat exchanger ...