Product Details

Product Introduction

Conventional Fire Alarm Control Panel with Four Zones

Main Parameter

·Four style B (class B) Initiating Device Circuits (IDCs)

·All zones accept two-wire smoke detectors and any normally-open contact devices

·One built-in, style Y (class B) Notification Appliance (Signal) Circuits (NACs)

·Alarm, trouble and supervisory, form-C relays standard

·24-volt operation

·Resettable four-wire smoke detector power @ 500mA

·Non-resettable power @ 500mA

·One-man walk-test programmable for silent or audible test

·Disable/enable control per IDC

·Reverse polarity protection