Home Companies Guangdong Sunkings Electric Co., Ltd

120Kva AC 400V 50/60Hz Perkins Engine Generator Set 6 Cylinders In Line

Guangdong Sunkings Electric Co., Ltd
Active Member

Contact Us

[China] country

Address: No. 1, Xinglong 2nd Road, Guanglong Industrial Zone, Chencun Town, Shunde, Foshan, China.

Contact name:Wayne Xie

Inquir Now

Guangdong Sunkings Electric Co., Ltd

120Kva AC 400V 50/60Hz Perkins Engine Generator Set 6 Cylinders In Line

Country/Region china
City & Province foshan guangdong
Categories Diesel Generators
InquireNow

Product Details

120Kva 400V Rated Voltage 50/60Hz Perkins Diesel Genset Stand By Generators

 

 

General Feature:

 

1. Prime power 100KW / 125KVA, standby power 110KW / 138KVA
2. Engine brand: Perkins
3. Alternator: Stamford
4. Water-cooled
5. Manual start / auto start
7. Soundproof canopy is optional
8. 230 / 400V AC, 50Hz / 60Hz, 0.8pF three-phase and four wires alternating current output

 

 

 

Genset modelSPS165

Genset Rated Power

Genset Standby Power

100kw / 120kva

110kw / 138kva

Rated voltage400/230V (adjustable)
Rated current180Amps
Frequency50 Hz / 60 Hz 
Power factor0.8 Lagging
Connecting type3 phase 4 wire
Cooling systemClosed cycle water-cooled with fan, water tank
Overall dimension (L×W×H) mm2750*850*1150
Gross weight (kg)1200

 

Diesel Engine
BrandPERKINS
Model1106A-70TAG1
Engine type6 cylinders in line, 4 stroke, direct injection
AspirationTurbocharged and intercooled
Rotating speed1500 RPM
Engine cooling systemWater-cooled
Fuel injection systemElectronic
Starting methodBy 24V batteries
Engine filter systemDry type air filter ,fuel filter, oil filter, water filter
Displacement(L)7
Bore×Stroke(mm)105×135
Compression ratio18.2:1
100% Load fuel consumption (l/h)≤205
Lube capacity(L)16.5

 

Alternator
BrandSTAMFORD
ModelUCI274D
Excite typeBrushless self-excited AVR regulation
Connecting type3 phase 4 pole
Steady frequency change0.50%
No load voltage≥95%-105%
Steady voltage≤±1%
Insulation classClass H
Protection gradeIP23

 

 

 

INSPECTION AND TEST

 

1 GENERAL

1.1 Each engine shall be tested at manufacturer’s workshop to certify the engine output and fuel consumption in accordance with the site operating condition specified by purchaser on the specification datasheet.

1.2 All relevant information drawings pertinent to the testing and test procedure shall be transmitted to the purchaser in advance of the test date notification.

1.3 The purchaser shall call for additional testing if test results are unsatisfactory or marginal. Any equipment rejected shall be repaired or replaced to the purchaser’s satisfaction and tests shall be repeated.

1.4 Any unsatisfactory material, equipment, installation, or workmanship shall be replaced or repaired to the purchasers satisfaction at the manufacturers cost.

1.5 The engine and generator shall be tested individually in accordance with relevant standards specified above.

1.6 The completed and individually tested engine and generator shall be assembled onto the base plate with all auxiliaries, instruments and controls for a complete test of the generator set.

 


 

Hot Products

63KVA Perkins Diesel Generator Set Water Cooled Diesel Genset Genset Specifications: Genset model ...
2250 Kva Perkins Diesel Genset , Open Type Diesel Generator Set, Perkins Power Generator Technical ...
120Kva 400V Rated Voltage 50/60Hz Perkins Diesel Genset Stand By Generators General Feature: 1. ...
150 Kva Perkins Diesel Genset 400 Rated Voltage 50/60Hz Commercial Generators General Feature: 1. ...
AC Perkins Diesel Generator 400Kva 50Hz 400V Output Voltage Diesel Power Generator Generator Set ...
220V/380V AC Three Phase Large Diesel Generator 500KW/625KVA Deutz Generator Set DEUTZ 320KW DIESEL ...