FUJIAN TECGEN POWER CO., LTD. |
Verified Suppliers
|
|
800kW diesel backup generator couple with AC alternator for Mining backup power
Key Features:
-With open frame type
-With SDEC 6 Cylinder diesel engine
-With Stamford / Leroy Somer / Mecc Alte / Chinese alternator
-With CHINT MCCB & Electronic Components
-Electric start with Varta Maintenance free battery
-8 hours Lasting Base Integrated fuel Tank
- Equipped with DEIF SGC-420 as standard controller
-Strictly comply with ISO9001/CE
-24*365 hours global after-sale services
-Option: ATS, Deepsea / ComAp controller
Warranty:
We provide 18 months or 1500 running hours service warranty for our diesel Backup generator. Once the service parts are required, the parts will be sent by Air.
800kW Diesel Backup Generator Datasheets:
800kW Diesel Backup Generator Specifications | |||||
Model | Engine | Alternator | Controller | Output | |
TG1000SD | 6KTAA25-G320 | TIG404S720 | DEIF SGC-420 | 563kVA | |
Remark: (1) Payment Terms: FOB Fuzhou Port (2) Delivery: 15 working days (3) Payment method: 30% deposit, 70% before delivery (4) Price Valid time: 30 Days (5) Option: Integrated Fuel Tank, Water Heater, ATS, PMG Generator, SYNC Function, 12/24 Hours Fuel Tank, 3000 hours Spare Parts
| |||||
General Date of 800kW Diesel Backup Generator | |||||
Engine Model | 6KTAA25-G320 SDEC | ||||
Alternator Mode | TIG404S720 | ||||
Rated Output | 900kVA / 720kW | ||||
Standby Output | 1000kVA / 800kW | ||||
Rated Speed | 1500 RPM | ||||
Frequency | 50 HZ | ||||
Rated Voltage | 240 / 415V | ||||
Rated Current | 1252.2A | ||||
Breaker | 1600 CHINT Breaker | ||||
ATS | 1600A ATS Cabinet for option | ||||
Power Factor | 0.8 | ||||
Genset Phase | 3 phase, 4 – wire connection | ||||
Fuel Tank | 8 running hours | ||||
Noise level dB(A) @7m | 85dB(A) | ||||
Net Weight | 5850KGS | ||||
Genset size | L4000 * W1800 * H2000mm | ||||
Voltage regulation rate | ≤±1% | ||||
Random voltage variation | ≤±1% | ||||
Frequency regulation rate | ≤±5% | ||||
Random frequency variation | ≤±0.5% | ||||
General specification of Engine for 800kW Diesel Backup Generator | |||||
Manufacture | SDEC | ||||
Model | 6KTAA25-G320 | ||||
Rated Output/Speed | 820KW/1500RPM | ||||
Standby Output/Speed | 902KW/1500RPM | ||||
Aspiration | Turbocharged & Intercooled | ||||
Speed Governor | ECU | ||||
Engine Type | 6 cylinders in line | ||||
Bore X Stroke | 170*185mm | ||||
Displacement | 25.2 L | ||||
Compression ratio | 18.4:1 | ||||
Cooling system | Forced Water Cooling Cycle | ||||
Rated speed | 1500rpm | ||||
Fuel Consumption/rated output | 197.1 L / h | ||||
Fuel Consumption/standby output | 219 L / h | ||||
Starter motor | D.C. 24V Electric starting | ||||
Alternator (Dynamo) | AC24V | ||||
General data of Alternator for 800kW Diesel Backup Generator | |||||
Alternator Model | TIG404S720 | ||||
Manufacture | Copy Stamford | ||||
Rate Output | 720kW | ||||
Rated voltage(V) | 240 / 415V | ||||
Voltage regulation | AVR ± 1.0 % | ||||
Working Altitude | ≤1000 | ||||
Control System | Brushless Self Excited | ||||
Bearing | Single Bearing | ||||
Insulation System | Class H | ||||
Protection | IP23 | ||||
Power factor | 0.8 | ||||
Winding connection | 3 phase, 4 – wire connection | ||||
Standard configuration of 800kW Diesel Backup Generator | |||||
Aluminum water tank | 50℃ | ||||
Controller Panel | DEIF SGC-420 | ||||
Battery | Varta Maintenance free Battery | ||||
Silencer | Included | ||||
Dry type air filter, fuel filter, oil filter | |||||
24V D.C automatic battery charger | |||||
Max. 50 degree celsius radiator | |||||
Batteries, rack and cable | |||||
Ripple flex exhaust pipe, flange and muffler |
Optional Features: