GDVA-404 Current Transformer Testing and Potential Transformer Testing Set
Introduction:
GDVA-404 CT PT Analyzeris performing excitation, ratio and phase error, polarity,
secondary loop burden and coil resistance on current and voltage
transformer. The instrument provides fully automatic testing and
calibration for all types of low leakage flux current transformer
and inductive voltage transformer. The maximum knee point voltage
of sample CT could be reached 8.4kv.
The standards support byGDVA-CT PT Analyzerinclude IEC60044-1, IEC60044-2, IEC60044-6 and C57.13
Application:
Tests for current transformer: | |
1 | Excitation curve and parameters test |
2 | Turns ratio test |
3 | Ratio and phase error test |
4 | Polarity mark check |
5 | Coil resistance measurement |
6 | Secondary loop burden measurement |
7 | Error line curve test for protection CT |
8 | Transient CT parameters test |
9 | CT nameplate guess |
10 | Saturation hysteresis loop curve measurement |
Tests for voltage transformer: | |
1 | Turns ratio test and phase angle error test |
2 | Polarity test |
3 | Secondary burden test |
4 | Coil resistance test |
Applications for CTPT analyzer: | |
1 | CT nameplate check |
2 | CT parameters check in work burden |
3 | CT transient parameters analysis |
4 | CT ratio and phase error calibration |
5 | PT routine test |
CTPT Analyzer Technical Index:
1 | Test standards | IEC60044-1, IEC60044-6, GB1208, GB16847, C57.13 |
2 | Power supply | AC220V±10%,50Hz/60Hz±10% |
3 | Power output | 0.1~180V (AC) |
4 | Current output | 0.001~5A(RMS) |
5 | Power output | 300VA |
6 | Maximum knee voltage measurement | 45kv |
7 | Current measurement | Range:0~10A (automatically change range in 0.1/0.4/2/10A) |
Error <±0.1%+0.01%FS | ||
8 | Voltage measurement | Range:0~200 V (automatically change range in 1V/10V/70V/200V) |
Error < ±0.1%+0.01%FS | ||
9 | Turns ratio measurement | Range :1~35000, |
1~2000 error<0.05% | ||
2000~5000 error>0.1% | ||
5000~35000 error<0.2% | ||
10 | Phase measurement | error:±2min,resolution:0.01min |
11 | Coil resistance measurement | Range:0~8kΩ (automatically change range in 2ohm/20ohm/80ohm/800ohm/8kohm) |
Error< 0.2%RDG+0.02%FS | ||
Maximum resolution:0.1mΩ | ||
12 | Temperature measurement | -50~100 Celsius degree,error<3 Celsius degree |
13 | CT Secondary burden | Range 0~160ohm (automatically change range in 2ohm/20ohm/80ohm/160ohm) |
Error <0.2%RDG+0.02%FS | ||
Maximum resolution 0.001ohm | ||
14 | PT Secondary burden | Range 0~80kohm (automatically change range in 800ohm/8kohm/80kohm) |
Error <0.2%RDG+0.02%FS | ||
Maximum resolution: 0.1ohm | ||
15 | PT ratio measurement | Range :1~35000, |
1~5000 error<0.2% | ||
5000~35000 error<0.5% | ||
16 | Saved data groups | >1000groups |
17 | Work condition | Temperature:-10°C~50°C,moist:≤90% |
18 | Size | 485mm×356mm×183mm |
19 | Weight | <15Kg |
Name | quantity | Description |
Host | 1 | |
3M mask cable | 2 | |
10M mask cable | 1 | |
Grounding cable 6M | 1 | Diameter size large than4MM |
Big test pliers | 2 | One red and one black |
Test gasket | 4 | Two red and two black |
Test pin | 4 | Two red and two black |
Test pliers | 4 | Two red and two black |
Power cable | 1 | |
Accessories bag | 1 | |
Production disk | 1 | Include Analysis application and instruction manual |
Instruction manual | 1 | |
Inspection report | 1 | |
Pass certificate | 1 |