Home Companies Chongqing Gold Mechanical&Electrical Equipment Co.,Ltd.

GDVA-404 Transformer Polarity CT PT Tester /CT PT Tester For Transformer

Chongqing Gold Mechanical&Electrical Equipment Co.,Ltd.
Active Member

Contact Us

[China] country

Address: 9F/10, Jintai Building, Nanping, Chongqing, China

Contact name:Daisy Tao

Inquir Now

Chongqing Gold Mechanical&Electrical Equipment Co.,Ltd.

GDVA-404 Transformer Polarity CT PT Tester /CT PT Tester For Transformer

Country/Region china
City & Province chongqing chongqing
InquireNow

Product Details

GDVA-404 Transformer Polarity CT PT Tester /CT PT Tester For Transformer

 

 

Tests for Current Transformer:

 

1) Excitation curve and parameters test

2) Turns ratio test

3) Ratio and phase error test

4) Polarity mark check

5) Coil resistance measurement

6) Secondary loop burden measurement

7) Error line curve test for protection CT

8) Transient CT parameters test

9) CT nameplate guess

10) Saturation hysteresis loop curve measurement

 

 

Tests for Voltage Transformer:

 

1) Turns ratio test and phase angle error test

2) Polarity test

3) Secondary burden test

4) Coil resistance test

 

 

Application:

 

1) CT nameplate check

2) CT parameters check in work burden

3) CT transient parameters analysis

4) CT ratio and phase error calibration

5) PT routine test

 

 

 

Technical Index:

 

1 Test standards: IEC60044-1, IEC60044-6, GB1208, GB16847, C57.13

2 Power supply: AC220V±10%,50Hz/60Hz±10%

3 Power output: 0.1~180V (AC)

4 Current output: 0.001~5A(RMS)

5 Power output:300VA

6 Maximum knee voltage measurement:45kv

7 Current measurement:

   Range:0~10A (automatically change range in 0.1/0.4/2/10A)

   Error <±0.1%+0.01%FS

8 Voltage measurement:

   Range:0~200 V (automatically change range in 1V/10V/70V/200V)

   Error < ±0.1%+0.01%FS

9 Turns ratio measurement:

   Range :

   1~35000,  1~2000 error<0.05%

   2000~5000 error>0.1%

   5000~35000 error<0.2%

10 Phase measurement: error:±2min,resolution:0.01min

11 Coil resistance measurement:

     Range:0~8kΩ (automatically change range in 2ohm/20ohm/80ohm/800ohm/8kohm)

     Error< 0.2%RDG+0.02%FS

     Maximum resolution:0.1mΩ

12 Temperature measurement:-50~100 Celsius degree, error<3 Celsius degree

13 CT Secondary burden:

     Range 0~160ohm (automatically change range in 2ohm/20ohm/80ohm/160ohm)

     Error <0.2%RDG+0.02%FS

     Maximum resolution 0.001ohm

14 PT Secondary burden:

     Range 0~80kohm (automatically change range in 800ohm/8kohm/80kohm)

     Error <0.2%RDG+0.02%FS

     Maximum resolution: 0.1ohm

15 PT ratio measurement:

     Range :1~35000, 1~5000 error<0.2%

     5000~35000 error<0.5%

16 Saved data groups:>1000groups

17 Work condition: Temperature:-10℃~50℃, moist:≤90%

 

Hot Products

GDVA-405 Current Transformer Analyzer,CT PT Analyzer 1.1 Application Tests for current transformer ...
GDVA-404 Transformer Turns Ratio Tester,Transformer CT PT Analyzer Tests for Current Transformer: 1) ...
GDVA-404 CT and PT Transformer TTR Tester Tests for Current Transformer: 1) Excitation curve and ...
GDVA-404 PT/CT Volt Ampere Characteristic Comprehensive Tester Tests for Current Transformer: 1) ...
GDVA-404 Transformer Polarity CT PT Tester /CT PT Tester For Transformer Tests for Current ...
GDVA-404 CT PT tester for Transformer / CT Analyzer Tests for Current Transformer: 1) Excitation ...