40.5KV Outdoor Frame - Type SF6 Circuit Breaker / High - Speed Air Circuit Breaker

Country/Region china
City & Province ningbo zhejiang
Categories Other Roadway Products
InquireNow

Product Details

40.5KV Outdoor Frame - Type SF6 Circuit Breaker / High-Speed Air Circuit Breaker

 

Overview

LW8-40.5 Type Outdoor AC HV SF6 Circuit Breaker is a kind of outdoor HV electrical equipment, three-phase, AC 50Hz. it is used not only for control and protection for 35kV power transmission and distribution system, but also for connecting circuit breaker and opening and closing capacitor bank, as well as for measurement and protection when it is equipped with current transformer.

This circuit breaker is equipped with CT14 type spring operating mechanism. And it is conformed to the requirements of the standard of GB1984-89 and IEC56 .

 

Application environment
a. Altitude to be not more than 1000m.
b. Ambient temperature: -30ºC - + 40ºC, the average value of 24H to be not more than 35ºC;
c. Relative humidity: the daily average value to be not more than 95%, monthly average value to be not more than 90%,
d. Speed of wind: not more than 35km/s
e. Contamination condition to be III grade, porcelain bushing creepage distance shall be 1050 mm (nominal creepage ratio to be not less than 25mm/kV);
f. The ambient air should be free of the flammable material, explosive danger, chemical corrosive and intensive shake.

 

Table 1

No.ItemUnitParameter
1Rated voltagekV40.5
2Rated insulation level1min power frequency withstand voltagekV185/215(fracture)
Lightning impulse withstand voltage95/118(fracture)
3Rated currentA2000
4Mechanical endurancetime5000
5Rated pressure of SF6 gas(20ºC meter pressure)Mpa0.45
6Locking pressure (20ºC meter pressure)Mpa0.40
7Lowest ambient temperatureºC-30
8Rated short-circuit breaking currentkA31.5
9Rated short-circuit making current(peak)kA80
10Rated short time withstand current(thermal current)kA31.5
11Rated peak withstand current(dynamic current)kA80
12Rated out-of-phase breaking currentkA7.9
13Breaking times of the rated short-circuit breaking current:time16
14Close times≤0.1
15Open times≤0.06
16Rated operation sequence O-0.3s-CO-180s-CO
17Rated breaking/opening current of single capacitor groupA400
18Last time of short circuit currents4
19SF6 leakage rate (yearly) ≤1
20Moisture Content of SF6 gas(20ºC)Ppm(v/v)≤150
21Rated operating voltage of spring operation mechanism  
Voltage of closing and opening coilVAC 220, 380
DC:48, 110 , 220
Voltage of energy storage motorVAC 220
DC 220
22Weight of SF6 gaskg8
23Weight of circuit breaker (including operation mechanism)kg1400


Table 2

No.ItemUnitTechnical RequirementsTest conditions and methods
1Travel of movable contactmm95±2Measurement of movable contact travel refer to darawing12
2Clearance between contactsmm605±1.5Measurement of Clearance between movable and fixed contact refer to drawing 12a
3Three-phase switch-on asynchronyms≤3Measurement of pole distance difference between movable and fixed contact refer to darawing14
4Three-phase switch-off asynchronyms≤2Measurement of pole distance difference between movable and fixed contact refer to drawing 15
5Resistance of main loopμΩ≤120Measurement to DC voltage drop method, put in 100A
6Speed at instant of contacts touchingm/s3.2±0.2Rated voltage and measurement method refer to drawing 14
7Speed at instant of contacts disconnectingm/s3.4±0.2Rated voltage and measurement method refer to the drawing 15
8Cuisine stroke of makingmm10+0.5 -0.1Refer to drawing 6 under the closing status
9positioning gap of Cuisine stroke of makingmm1-2Refer to drawing 6 under the closing status
10Partial charging
40.5kV
25.7kV
PC20At rated gas pressure, use partial instrument to put 40.5kV between two outgoing wires for 1min, then drop to 25.7kV equably
PC10

Hot Products

6 ~ 35 KV / 30 ~ 2500 KVA Resin Casting Dry Type Distribution Transformer ​ General: As the ...
30 ~ 2500 KVA Thin - Insulation Resin Cast Dry Type Power Transformer General: 10 KV grade SCB10, ...
Indoor 10 KV Three phase Resin Cast Dry - type Power Distribution Transformer​ Overview: SC(B)10 ...
35kv / 20kv / 10kv Electrical Dry Type Distribution Transformer NINGBO TIANAN (GROUP) CO., LTD. ...
6.6 kV SCB Three Phase Cast Resin Dry Type Distribution Transformer Product Description SC(B)10 ...
Power Distribution Air Cooled Transformer Scb Series Dry Type Electrical Transformers Overviews SG(H...