Guangzhou Hiseer Air Conditioning Co.,Ltd |
Air to water heat pump efficiency heats or cools your house
AW10-DNNNS, HISEER heat and cool system with stainless steel
cabinet, 380-415V/3/50Hz, all year round used, energy saving heat
pump: heats or cools your house as well as offers domestic hot
water.
Air-source heat pump, often used in moderate climates, moves energy
from the air into the building for heating or cooling and
domestic hot water. Even at temperatures as low as -20˚C, an air
source heat pump can supply significantly more energy than it uses
– and with no local C02 emissions, it helps reduce impact on the
environment.
HISEER heat pumps adopt the following world famous parts:
Heat pumps are measured by their coefficient of performance (COP). The COP for air source heat pumps is very similar to that for ground source heat pumps at approximately 2-4. With a COP for instance of 4, 4 units of heat are produced for every 1 unit of electricity consumed. (The three free units of heating were extracted from the outside air). Even with ambient air temperatures of -10 to -15 degrees Celsius, an air source heat pump can extract useful heat (i.e. > 1 unit of heat generated per unit of electricity consumed).
Advantages:
AW10-DNNNS
AIR TO WATER HEAT PUMP | AW10-DNNNS | |
Heat output/Power consumption at 7/35℃ | kW | 11.0/2.9 |
Heat output/Power consumption at 7/45℃ | kW | 10.5/3.3 |
Heat output/Power consumption at 7/55℃ | kW | 10.2/4.1 |
Heat output/Power consumption at 2/35℃ | kW | 9.5/2.8 |
Heat output/Power consumption at 2/45℃ | kW | 9.2/3.4 |
Heat output/Power consumption at -7/35℃ | kW | 7.2/2.8 |
Heat output/Power consumption at -7/45℃ | kW | 7.1/3.4 |
Starting current | A | 46 |
Power |
| 380-415V/3PH/50Hz |
Compressor |
| HITACHI scroll |
Condenser |
| Brazed plate heat exchanger |
Nominal flow heating medium | l/s | 0.52 |
Internal pressure drop at nominal flow | kPa | 24 |
Air flow | m3/h | 3000 |
Nominal output fan | W | 220 |
Max outgoing heating medium temperature | ℃ | 55℃ |
Dimensions(HxWxD) | mm | 1050x1050x450 |
Pipe connector |
| DN25 |
Weight | kg | 125 |
The above data is tested by EN14511