F 3330: 8-channel output module
safety-related, applicable up to SIL 3 according to IEC 61508
•resistive or inductive load up to 500 mA (12 W)
•lamp load up to 4 W
•with integrated safety shutdown, with safe isolation
•no output signal with break of the L- supply
Figure 1: Block diagram and front cable plug
The module is automatically tested during operation. The main test routines are:
–Reading back of the output signals. The operating point of the 0-signal read back is
≤ 6.5 V. Up to this value the level of the 0-signal may arise in case of a fault and this will not be detected
–Switching capability of test signal and cross-talking (walking-bit test).
Outputs 500 mA, short-circuit-proof
Internal voltage dropmax. 2 V at 500 mA load
Admissible line resistance (in + out) max. 11 Ω
Undervoltage trippingat ≤ 16 V
Operating point f. short-circuit current0.75...1.5 A
Outp. leakage currentmax. 350 μA
Output voltage if output is resetmax. 1.5 V
Current input WDmax. 30 mA
Monitored switching timemax. 200 μs
Space requirement4 SU
Operating data5 VDC / 110 mA
24 VDC / 180 mA plus load

 

F 3322: 16-channel output module
resistive or inductive load up to 500 mA (12 W), lamp connection up to 12 W
with safe isolation
no output signal at break of the L- supply
Block diagram
Planning note
Only max. 10 output modules with nominal load may be used in one I/O subrack, and not more
than half of the possible output loads of 16 x 0.5 A (= 8 A) may be switched on at the same time.
The standard fusing of the modules in the I/O subrack is 4 A slow blow.
Outputs k short-circuit proof, 500 mA
Response value for
current limiter > 550 mA
Space requirements 4 SU
Operating data 5 V DC / 110 mA
24 V DC / 150 mA plus load

 

F 3237: 8-channel input module

safety-related, applicable up to SIL 3 according to IEC 61508,
• for the connection of safety-related proximity switches,
proximity switches according to EN 60947-5-6 (NAMUR) and
resistor-wired sensors
• monitoring of the lines for short-circuit and line break

Appertaining function block: HB-RTE-3
The module is automatically tested completely during operation. The main test routines are:
- Switch on and switch-off capability
- Crosstalk of the input circuits by walking-zero
- Function of the input filters
- Correct function of the module
The function of LEDs are not tested.
Switching time approx. 10 ms
Operating points IE
0-signal 0.35 ≤ IE ≤ 1.2 mA
1-signal 2.1 ≤ IE ≤ 6.0 mA
wire break ≤ 0.28 mA
short circuit ≥ 6.5 mA
Line impedance ≤ 50 Ω (acc. to EN 60947-5-6)
Line length ≤ 1000 m (∅ = 0.5 mm2)
Supply voltage US 8.2 V
Shunt R* 681 Ω; 1 %; 0.25 W
(R17...R24) part no. 00 0751681
Space requirement 4 SU
Operating data 5 VDC / 90 mA; 24 VDC / 170 mA

 

BV 7055: Data connecting cable
Connection of bus terminal H 7506 to converter Edgeport/2i (USB / RS 485)
in systems H41q/H51q
Standard lengths: 2 m , 4 m

 

BV 7046: Data connecting cable
Connection of the bus terminal H 7506 to the interface in the
H41q/H51q systems (redundant systems)
Standard lengths: 2 m, 4 m

 

HIMA devices for current distribution
It is recommended to use the HIMA supplies and current distributions:
4.1.2 Supply 24 VDC
The 24 VDC power supply can be feeded three times to the system H51q-HS/HRS (starlike
wiring). See also catalog H41q/H51q, chapter 4.3, The Input/Output Level, 24 VDC Supply and
Distribution.
4.1.3 Output 24 VDC
With installation of the assembly kit a conductive connection to the
frame or a separate earth connection has to be installed according to
the EMC requirements.
Connection PE earth: Faston 6.3 x 0.8 mm.
Pay attention for the manufacturers information concerning detaching
and replugging of the Faston connectors!
K 7212 redundant feeding up to 35 A total current, with 2 decoupling diodes and 2 network
filters, with fusing of up to 12 single circuits with circuit breakers or
K 7213 redundant feeding up to 35 A total current, with fusing of up to 12 single circuits
with circuit breakers or
K 7214 redundant feeding up to 150 A total current, with fusing of up to 18 single circuits
with circuit breakers or
K 7215 redundant feeding up to 150 A total current, with fusing of up to 18 single circuits
with circuit breakers, graphical display.

 

Communication modules F 8627/F 8628, F 8627X/F 8628X
Right of each central module of the H51q-HS/HRS PES up to five communication modules can
be installed. The communication module mainly contains:
– 32-bit RISC microprocessor
– Operating system
– RAM for further protocols
– F 8627 Ethernet interface (safeethernet, OPC, ...)
F 8628 Profibus-DP slave interface
– Dual port RAM (DPR) for the communication with the central module via CPU bus
Special applications with the communication module F 8627X:
– connection of the central module to a PADT (ELOP II TCP)
– connection to other communication partners within an Ethernet network (Modbus TCP)
Special application with the communication module F 8628X:
– ELOP II TCP connection (PADT) via the Ethernet interface of the F 8628X to the H41q/
H51q controller

 

Coprocessor module F 8621A

Right of each central module of the H51q-HS/HRS PES up to three coprocessor modules can
be installed. The coprocessor module mainly contains:
– Microprocessor HD 64180 with a clock frequency of 10 MHz
– Operating system EPROM
– RAM for a PLC master project
– Two interfaces RS 485, via communication software function block setting of the baud rate
up to 57600 bps
– Dual port RAM (DPR) for the communication with the central module via CPU bus

 

HRS contains the essential functions demonstrated in the block diagram of the central module:
Figure 2: Block diagram of the central module F 8650X
– two clock-synchronized microprocessors
– each microprocessor with an own memory, one processor operates with real data and program
and the other one with inverted data and program
– testable hardware comparer for all the external accesses of both
microprocessors, in case of a fault the watchdog will be set to the safe status and the status
of the processor is announced
– Flash-EPROMs of the program memory for the operating system and the user program
usable for min. 100,000 writing cycles
– Data memory in sRAM
Note Operating system/resource type in ELOP II
The assembly kit is usable since operating system BS41q/51q V7.0-8.
Resource type in ELOP II: H51qe-HS/H51qe-HRS.
Watchdog
B 5233-1/-2 / H51q-HS/HRS (0605)
3/14
– Multiplexer to connect I/O bus, DPR and redundant CU
– Battery backup of the sRAMs via batteries with monitoring
– 2 interfaces RS 485 with galvanic isolation. Transm. rate: max. 57600 bps
– 4digit diagnostic display and 2 LEDs for information out of the system, I/O level and user
program
– Dual Port RAM for fast memory access to the second central module
– Hardware clock, battery buffered
– I/O bus logic for the connection to the input/output modules
– Watchdog
– Power supply monitoring, testable (5 V system supply)
– Battery monitoring

 

B 5233-1/-2: Assembly Kit /
H51q-HS/HRS: System
System H51q-HS/HRS in K 1412B system subrack, 5 HU, 19 inches with redundant central
module, power supply 24/5 V, power supply monitoring module, I/O bus connection, communication
modules (optional), coprocessor modules (optional) and three fans
H51q-HS / B 5233-1: single channel bus, redundant central modules
H51q-HRS / B 5233-2: redundant bus, redundant central modules
TÜV certified, applicable up to SIL 3 according to IEC 61508

 

Parts of the B 5233-1/-2 assembly kit /
H51q-HS/H51q-HRS system
• 1 x K 1412B central rack, 5 units high, 19 inches, with cable tray with three fan modules
K 9212, hinged receptacle for the label and backplane Z 1001.
• additional modules on the rear
• 3 x Z 6011 decoupling and fusing to feed the power supply modules
• 1 x Z 6018 fan run monitoring and fuse monitoring
• 2 x Z 6013 decoupling and fusing of the supply voltage for the WD signal
• 2 x F 7546 bus termination module (B 5233-1)
• 4 x F 7546 bus termination module (B 5233-2)
• 1 x BV 7032 data cable (only B 5233-1)
includes the modules:
• 3 x F 7126 power supply modules 24 V / 5 V, 10 A (PS1, PS2, PS 3)
• 1 x F 7131 power supply monitoring
• 2 x F 8650X central modules (CU1, CU2)
modules for option (separate order)
• 6 x F 8621A coprocessor modules (CM11 - CM13, CM21 - CM23)
• 10 x communication modules (CM11 - CM15, CM21 - CM25)

Assembly kits to be used for the I/O level:
• B 9302 I/O subrack 4 units high, 19 inches
• B 9361 additional power supply, 5 VDC, 5 units high, 19 inches
The max. current must be 18 A (all I/O modules and the modules in the central rack), if
3 x F 7126 are used to keep the system in operation even one power supply module F 7126
has failed.
Values of the current requirement (+5 VDC) refer to the data sheets.

 

 

 

 

 

 

 

 

 

 

 

 

Hot Products

Spectral Physics laser 532nm J40-X15SC-532QA http://www.spectra-physics.com/assets/client_files...
Nine to new Keyence laser 3D marking machine keyence md-v9920 Belt MC-P1 handheld Terminal
keyence Vision Controller cv-x100a If you have special needs, please contact us in time. There are ...
Controller cv-3001+2 A CCD intelligent camera cv-035m+ control handle complete set 9.5 into new 1, ...
Japan Keene Keyence High Precision Laser Displacement controller 1. Model: lk-g3001+ sensor lk-g32...
Keyence Vision System 1.cv-x100m+cv-035c+ Handle Complete Set 2. Spot 1 Sets! If you have special ...