Chongqing ASSEN Power Equipment Co.,LTD |
|
Usage:
ASSEN ZYD-I Transformer Oil Regeneration system has been specially designed for on site use to completely regenerate insulating oils in de-energized transformers. Besides provides regular oil purification such as degassing, drying and particulate removal, it also can remove acidity, sludge, other soluble oil decay products and discoloration. After treating, the oil can be reused as new.
Fast remove moisture, gas ,particles, acidity, free carbon, and other soluble oil decay products in transformer oil, mutual inductor oil, cable oil, and circuit breaker oil, and restore property of insulating oil.
Advantage:
1.It can treat deteriorated transformer oil.
2.It can significantly improve oil color. Dark-colored oil can be retrofitted to the color less than 1.5.
3.It can recover aging insulating oil electrical with PH value ≥5.5, acid value ≤0.03 mg koH/g, or dielectric loss factors tgδ (90℃) ≤0.001 back to new oil characteristics.
4.Economical. Extremely dirty oil can be reused after regeneration. The cost of purchasing regenerated oil is typically less than 90% of new oil.
5.Control of strategic asset is retained. Oil in use is an asset. Use of regeneration technology removes dependence of the oil company on replacement suppliers and isolates them from wildly fluctuating external market prices.
6.Extended life of power transformer equipment.
Technical Data
Parameters | Unit | ZYD-30 | ZYD-50 | ZYD-100 | ZYD-150 | ZYD-200 | ZYD-250 | ZYD-300 | |
Flow | L/min | 30 | 50 | 100 | 150 | 200 | 250 | 300 | |
Working vacuum | MPa | 0.08 ~ 0.099 | |||||||
Working Pressure | MPa | ≤0.3 | |||||||
Breakdown Voltage | KV | ≥75 | |||||||
Water Content | PPM | ≤3 | |||||||
Gas Content | % | ≤0.01 | |||||||
Impurity Size | μ | ≤5 | |||||||
Temperature Range | ℃ | 20 ~ 80 | |||||||
Power | Three Phase 50HZ380V(as per the customer's requirements) | ||||||||
Working Noise | dB(A) | 75 | 75 | 75 | 80 | 80 | 80 | 80 | |
Heating Power | kW | 30 | 30 | 45 | 60 | 75 | 90 | 120 | |
Total Power | kW | 35.5 | 37.5 | 52.5 | 71.4 | 86.5 | 102.5 | 135 | |
Inlet/Outlet | mm | φ25 | φ32 | φ42 | φ50 | φ50 | φ60 | φ60 | |
Weight | kg | 600 | 800 | 1050 | 1400 | 1800 | 2000 | 2200 | |
Overall | Length | mm | 1050 | 1100 | 1200 | 1450 | 1600 | 1800 | 1900 |
Width | mm | 750 | 800 | 950 | 950 | 1100 | 1200 | 1200 | |
Height | mm | 1350 | 1400 | 1500 | 1650 | 1800 | 1900 | 1900 |
The oil’s performance after treatment:
Moisture | PPM | ≤3 |
Gas content | % | ≤0.01 |
Impurity size | μ | ≤1 (no free carbon) |
Breakdown voltage | kV | ≥75 |
IFT | dynes/cm | ≥40 |
Acid value | mgKOH/g | ≤0.03 |
Dielectric loss factors | tgδ(90°C) | ≤0.001 |
Please contact us for more details.