CN Cable Group Co., Ltd. |
|
Tinned copper conductor with AL/PE laminate together with braid of
annealed and
tinned copper wires shield TEL cable
Application
Halogen free, shielded and flexible connecting cable for use in
telecom equipment where there are
requirements for low inductance and good temperature resistance.
Suitable in areas that require high electromagnetic compatibility.
Grey jacket for indoor use. Black jacket is sunlight resistant, for
outdoor use. UL listed, “cable tray use” (E194163)
Conductor
Stranded, annealed copper, tinned, flexible, according to IEC
60228, class 5. Three parallel cores to form a flat conductor.
Insulation
Flame retardant polyethylene, black and grey.
Shield
AL/PE laminate together with braid of annealed and tinned copper
wires + Al-polyester foil.
Sheath
Flame retardant polyethylene, grey or black.
Operating voltage
Max 600V
Operating temperature
Max 90ºC, dry
Fire resistance
IEC 60332-3 cat C
UL 1685, Vertical Tray
Technical Data
Conductors x size | Height x Width, nom (mm) | Weight/100m | Resistance
| ||
Conductor | Insulation | Sheath | (kg) | (ohm/km) | |
2 x 14 AWG (2,5mm²) | 2,4 x 4,9 | 7,3 x 7,0 | 10,0 | 8,21 | |
2 x 10 AWG (6mm²) | 3,2 x 6,4 | 9,4 x 9,4 | 19,3 | 3,39 | |
2 x 10 AWG (6mm²) | 3,2 x 6,4 | 9,4 x 9,4 | 19,3 | 3,39 | |
2 x 8 AWG (10mm²) | 3,8 x 9,0 | 10,5 x 11,5 | 29,2 | 1,95 | |
2 x 8 AWG (10mm²) | 3,8 x 9,0 | 10,5 x 11,5 | 29,2 | 1,95 | |
2 x 6 AWG (16mm²) | 4,6 x 11,0 | 11,8 x 13,6 | 42,6 | 1,24 |
Ordering information:
Conductors x size | Length (m) | Drum | Total weight (kg) |
2 x 14 AWG (2,5mm²) | 500 | Bobbin | 52 |
2 x 10 AWG (6mm²) | 500 | K6 | 104 |
2 x 10 AWG (6mm²) | 500 | K6 | 104 |
2 x 8 AWG (10mm²) | 500 | K6 | 153 |
2 x 8 AWG (10mm²) | 500 | K6 | 153 |
2 x 6 AWG (16mm²) | 300 | K6 | 135 |