AMAXPOWER NEW ENERGY TECH CO., LTD |
|
Amaxpower CL Series 2V Industry Gel Battery For Solar and UPS System (2V 1500Ah)
Amaxpower CL Series 2V Sealed Lead Acid Gel Battery Deep Cycle Long Life Industry AGM Battery for emergency systems
AMaxpower 2V Batteries : CL Sereis Deep Cycle Gel Battery and CG Series Deep Cycle AGM Battery
Certificates: ISO9001/14001/18001 ; CE/IEC 60896-21/22 / IEC 61427 Approved
AMaxpower CL Series 2V Deep cycle gel battery is high -temperature sealed free maintenance deep cycle gel battery with 15-20 years life in float service,designed for frequent cycle applications,Suitable for solar, CATV,Marine,industry,RV and deep discharge UPS,communication and telecommunication,etc.
Chinese Best Quality Deep Cycle GEL Battery Applications:
Φ Communication equipment Φ Telecommunication control equipment Φ
Emergency lighting systems Φ Electric power systems Φ Power station
Φ Nuclear power station Φ Solar powered and wind powered systems Φ
Load leveling and storage equipment Φ Marine equipment Φ Power
generation plants
Φ Alarm systems ΦUninterruptible power supplies and stand-by power
for computers Φ Medical equipment Φ Fire and security systems Φ
Control equipment
Φ Stand-by electric power.
Specification
Nominal Voltage | 2V (Single cells) | |
Nominal Capacity | 1500Ah@10 hour-rate | |
Dimension | Length | 401±2(15.8 inches) |
Width | 351±2(13.8 inches) | |
Height | 344±2(13.5 inches) | |
Total Height | 369±2(14.50 inches) | |
Weight | Approx. 100kg (220.5lbs) | |
Reference Capacity (25°C/77°F ) | 20 hour rate (78.8A) | 1575Ah |
10 hour rate (150A) | 1500Ah | |
5 hour rate (270A) | 1350Ah | |
3 hour rate (400A) | 1200Ah | |
1 hour rate (975A) | 975Ah | |
Max. Discharge Current (25°C/77°F) | 5250A (5S) | |
Internal Resistance | Full charged at 25℃(77°F): Approx. 0.3mΩ | |
Charge (Constant Voltage) (25°C/77°F) | Cycle Use | Voltage: 2.33-2.37V@25℃(77°F) Initial Charging Current: Less than 300A |
Float Use | Voltage: 2.24-2.28V@25℃(77°F) | |
Operating Temperature Range | Discharge | -20~60°C |
Charge | -10~60°C | |
Storage | -20~60°C | |
Nominal Operating Temperature Range | 25°C ±3°C(77±3°F) | |
Capacity affected by Temperature (20 hour rate) | 40°C(104°F) | 102% |
25°C(77°F) | 100% | |
0°C(32°F) | 85% | |
-15°C(5°F) | 65% | |
Self-Discharge (25°C/77°F) | After 3 month | 91% |
After 6 month | 82% | |
After 12 month | 64% | |
Container Material | ABS Plastic |
Industry use, Communication equipment, Telecommunication control equipment; Emergency systems; Electric power systems; Golf carts; Caravan; Power station; Nuclear power station; Solar power and wind power systems; Load leveling and storage equipment; Marine equipment; Power generation plants; Alarm systems, UPS and inverters; Medical equipment; Fire and security systems, Control equipment; Stand-by electric power.