Home Companies SUZHOU FOBERRIA NEW ENERGY TECHNOLOGY CO.,LTD.

181*77*167mm F14 12v 20ah Lead Acid Battery UPS Low Self Discharge

SUZHOU FOBERRIA NEW ENERGY TECHNOLOGY CO.,LTD.
Active Member

Contact Us

[China] country

Address: No.188 Chunxu Road ,Economic Development Zon, Kunshan City, Suzhou, Jiangsu Province, China.

Contact name:Roger Ning

Inquir Now

SUZHOU FOBERRIA NEW ENERGY TECHNOLOGY CO.,LTD.

181*77*167mm F14 12v 20ah Lead Acid Battery UPS Low Self Discharge

Country/Region china
City & Province suzhou jiangsu
Categories Batteries
InquireNow

Product Details

Low Discharge Rate Ups Battery 12v 20ah Lead Acid Battery Ups For Solar System

 

>Main Features

 

1. Using oxygen recombination technology: maintenance-free;


2. PbCaSn alloy for plate grids: less gassing, less self-discharging;


3. High quality AGM separator: extend cycle life and prevent micro short circuit;


4. ABS material: increase the strength of battery container. (Flame-retardant ABS is optional);


5. High purity raw material: ensure low self discharge rate;


6. Silver-coated copper terminals (T1, T2 terminal), brass insert terminals and lead terminals improve the electric conductivity.

 

7. 100% Pre-delivery inspection to ensure stable quality and reliable performance.

 

 
>Specification
 
Battery Model No.FBR12V20Ah
Nominal Voltage12V
Capacity
(25ºC)
20HR(5.25V)20Ah
10HR(5.25V)18.7Ah
1HR(4.80V)13Ah
DimensionLength181±2mm
Width77±1mm
Height167±2mm
Total height167±2mm
Approx. Weight5.7kg±4%
Terminal typeF14
Internal resistance
(Fully charged,25ºC)
Approx 14
Capacity affected by
temperature(20HR)
40ºC102%
25ºC100%
0ºC85%
-15ºC65%
Self-discharge
(25ºC)
3monthRemaining Capacity:91%
6monthRemaining Capacity:82%
12monthRemaining Capacity:65%
Nominal operating temperature25ºC±3ºC(77ºF±5ºF)
Operating
temperature range
Discharge-15ºC-50ºC(5ºF-122ºF)
Charge-10ºC-50ºC(14ºF-122ºF)
Storage-20ºC-50ºC(-4ºF-122ºF)
Float charging voltage
(25ºC)
13.5 to 13.8V
Temperature compensation:-18mV/ºC
Cyclic charging voltage
(25ºC)
14.5 to 15V
Temperature compensation:-30mV/ºC
Max charging current6A
Max discharging current300A(5sec.)
Designed floating life(20ºC)5years
 
>Structure and composition
 
ComponentPositive plateNegative plateContainerCoverSeparatorElectrolyteSafety valveTerminal
Raw materialLead dioxideLeadABSABSAGMSulfuric acidRubberCopper
 
 
>Constant Current Discharge Characteristics(A,25ºC)
 
F.V/Time10min15min30min60min2h3h4h5h8h10h20h
9.6V87.267.240.224.714.610.48.407.184.944.072.16
9.9V84.665.639.424.314.510.38.367.144.914.062.15
10.2V81.163.238.223.714.410.38.307.094.874.052.13
10.5V77.661.037.323.214.210.28.247.044.844.032.13
10.8V73.257.835.922.513.89.897.996.834.694.002.12

 

>Constant Power Discharge Characteristics(Watt,25ºC)

 

F.V/Time10min15min30min60min2h3h4h5h8h10h20h
9.60V94273845128216912298.884.958.648.625.9
9.90V91472044227816812298.384.458.348.525.8
10.2V87669442827116712197.683.857.948.425.8
10.5V83867041826516412096.983.257.548.125.6
10.8V79163540325716011694.080.755.847.825.4
 
 
>Application

1.Electrical toys&tools;

2.telecom system;

3.fire&security&alarm system;

4.emergency lightening system;
 
 
 
>Workshop scene
 
>FAQ

Q1: How to choose the right battery?
A1: Tell us your demand, then our sales will recommend a suitable battery for you.

Q2. Do you have any MOQ limit?
A2: Yes, we have MOQ for mass production, it depends on the different model numbers.

50-500pcs sample order is available. for sample checking is available.

Q3. Is it OK to print my logo on the product?
A3: Yes. Please inform us before production and confirm the design according to our samples.

 

Q4: How can you tell if a battery is good or bad?

A: You should first check the battery for defects such as a broken circuit, a short, or a broken container. If an outward problem
is not apparent, then you will have to check the battery's capacity using known measuring techniques to ascertain the problem.

 

Q5: How to maintain the battery?
A:The battery should be stored in clean, dry, ventilated, dark environment when not using, keep it after full charge, recharge it every 3 months or 6 months.

 
 
 

Hot Products

Wholesale sealed lead acid battery 12v 100ah 10Hr vrla sealed lead acid battery For UPS back up ...
AGM sealed lead acid batteries 12V65Ah vrla sealed lead acid battery F14 Terminal > Specification ...
12 volt sealed lead acid battery 120Ah/10Hr maintenance free sealed lead acid battery for storage ...
Factory sealed lead acid battery maintenance 12V 90ah 100ah For back up power System > Specification ...
Factory sealed lead acid batteries 12V 65AH Deep Cycle UPS Rechargeable vrla sealed lead acid ...
Factory rechargeable sealed lead acid battery 12v 120ah for solar energy systems > Product ...