Flatpack2 220/10 HE 220V 10A Eltek Rectifier Module 241119.815

 

Applications

 

Data Center

Power Utilities

Power Stations

Switch Tripping

Converter Stations

Emergency Lighting

Railway Infrastructure

Marine And Off-Shore

Central Power System

Central Power System

Dc/ Dc - Isolate Branches

Control & Protection Systems

 

Description

 

High efficiency and reliable rectifiers

The most efficient power conversion module in the industry! Since the launch the Flatpack2 family has expanded into a wide selection of power ratings and voltages.

Power systems up to the MW-range can be realized using the 10A model addressing small and larger modular data centers’ power needs. 220VDC power systems provide an excellent alternative to traditional AC UPS providing significant efficiency and reliability improvements.

With 220V DC, standard components, cables and distribution can be used and most IT equipment designed for 208/ 230V AC can be connected directly to the 220V DC bus.

 

Specifications

 

Part number241119.815
Model220 / 10A HE
INPUT DATA 
Voltage range85 - 305 V AC
Voltage range (nominal)176 - 305 V AC
Frequency45 - 66 Hz
Maximum current17 ARMS
Power Factor0.99 (@ 50-100% load)
THD (@ 230 VAC)< 4% (@ full load)
ProtectionVaristor for transient protection, fuse in both lines, shutdown above 300/ 305 V
OUTPUT DATA 
Default voltage245.3 V DC
Voltage range

198 1) - 280 VD 2)

C

# Pb cell supported (1.8 - 2.4 V DC/ cell)108-110 (120 3))
# NiCad cell supported (1.05 - 1.65 V DC/ cell)-
Max power, nominal input2800 W
Max power, 85V input1304 W
Max current, @220V DC10 A 4)
Hold-up time, default voltage and 1500 W load20 ms, VOUT > 210 V DC
Ripple and noise, 30 MHz bandwidth< 1000 mV PP
Current sharing±5% of maximum current from 10 to 100% load
Static voltage regulation±0.5% from 10% to 100% load and nominal input
Dynamic voltage regulation±5.0% for 10-90% or 90-10% load variation, regulation time < 50ms
ProtectionOvervoltage shutdown, short circuit proof, high temperature, hot plug -in inrush current limiting, ORing diode
OTHER SPECIFICATIONS 
Efficiency> 95.5%
Isolation3.0 kVAC – input to output, 1.5 kV AC – input to earth, 1.5 kV DC – output to earth 3 kVAC – CAN to input, 3 kV AC – CAN to output, 500 V AC – CAN to earth
Alarms (Red LED)Low mains shutdown, High and low temperature shutdown, Rectifier Failure, Overvoltage shutdown on output, Fan failure, Low voltage alarm, CAN bus failure
Warnings (Yellow LED)Rectifier in power derate mode, Remote battery current limit activated, Input voltage out of range, flashing at overvoltage
Normal (Green LED)Input and output ok
MTBF (Telcordia SR-332 Issue I method III (a))>400 000h (@T AMBIENT= 25°C)
Operating temperature (5 - 95% RH non-cond.) Output power de-rates above temp / to

-40 to +75°C [ -40 to +167°F]

+50°C / 1750 W @ +75°C

Storage temperature-40 to +85°C (-40 to +185°F), humidity 0 - 99% RH non-condensing
Dimensions[WxHxD] / Weight109 x 41.5 x 327mm (WxHxD) [4.25 x 1.69 x 13”] / 1.950 kg [4.3lbs]
DESIGN STANDARDS 
Electrical safetyUL 60950 -1, EN 60950 -1, CSA 22.2
EMC

ETSI EN 300 386 V.1.3.2

EN 61000-6-1 / -2 / -3 / -4 / -5

Mains HarmonicsEN 61000 -3-2
Environment

ETSI EN 300 019: 2-1 (Class 1.2), 2-2 (Class 2.3) & 2-3 (Class 3.2)

ETSI EN 300 132-2

2011/ 65/ EU (RoHS) & 2008/ 98/EC (WEEE)

Marine compliance

(EMC class B with AC filter)

 

-

 

  • VOUT may increase at no and very light load (< 1 A) for V OUT_SET < 245 V DC set and V IN > 250 V AC/ DC
  • Specification valid for HW version 2 and newer. For older revision see DS:24111x.815.DS3 ver1.
  • VRLA batteries boost 2.33V/ cell
  • 8A when V IN > 290V AC and Tambient > 45°C and VOUT < 220V DC

SMARTPACK2 MASTER AND BASIC INDUSTRIA

FLATPACK2 POWER RACKFOR HVDC PN268035

Hot Products

2-port 100M Ethernet Media Converter IEEE 802.3u 100Base-TX and 100Base-FX Features Support 1 100M ...
2-port 100M Industrial Media Converter Management Card Features Support 2 100M copper ports Input ...
2-port 100M Industrial Media Converter Unmanaged Daughter Card Overview The series adopt industrial ...
2-port 100M Unmanaged Industrial Media Converter Features Support 1 100M fiber port, 1 100M copper ...
3-port 100M Transceiver IP40 Optic Unmanaged Industrial Media Converter Features Support 1 100M ...
3 Port Fast Automatic Flow Control Transceiver Ethernet to Fiber Media Converter Features Support 1 ...