Flatpack2 48V 2000W Super HE Eltek Rectifier Module 21119.106

 

APPLICATIONS

 

TELECOM - WIRELESS

Radio base station / Cell sites

LTE / 4G / WiMAX

Mobile switching center (MCS)

Microwave

Broadband

TELECOM - FIXED

Central office

Telephony servers / switches

Fiber optics

Microwave

Broadband

Broadcast

Data center

 

Key Features

 

SUPER HIGH EFFICIENCY – 97.8%

HIGH POWER DENSITY – 33 W/IN3

COMPATIBLE WITH EXISTING SYSTEMS

GLOBAL COMPLIANCE

PATENTED TECHNOLOGY

HOT PLUGGABLE

 

Super High Efficiency (SHE) rectifiers for Telecom applications

 

The Flatpack2 48V Super HE rectifiers are contributing to setting the new industry standard for efficiency in the DC power market.

With an efficiency of 97.8% the Super HE is a premium rectifier particularly suitable for markets and applications where the energy is costly. In grid connected applications the payback time is down to 2 years compared to standard HE rectifiers, and in hybrid applications even faster.

The Flatpack2 Super HE is fully compatible with Flatpack2 and Flatpack2 HE systems and can replace any Flatpack2 48V rectifier module.

 

Specifications

 

Model48/3000 SHERemarks
Part number241119.106 
INPUT DATA  
Voltage (nominal range)206 - 264 VAC 
Voltage (operating range)85 - 264 VAC 
Frequency45 - 66 Hz 
Maximum current16 ARMS 
ProtectionFuse in Live, varistor for transient protection, shutdown when VIN is out of range 
OUTPUT DATA  
Voltage (default)53.5 VDC 
Voltage (adjustable range)43.21) - 57.6 VDC 
Max power, nominal input3000 W 
Max power, de-rated @VIN = 85 VAC1000 W 
Max current, @VOUT = 48 VDC62.5 A 
Current sharing±5.0% of max current 
Static voltage regulation (10-100% load)±0.5% 
Dynamic voltage regulation±5.0% for 10-90% or 90-10% load variation, regulation time < 50ms 
Hold up time (3000W load)>10ms; output voltage > 42 VDC 
Ripple<150 mVPP , 30 MHz bandwidth 

 

Protection

Overvoltage shutdown, short circuit proof, high temperature, hot plug-in inrush current limiting, fuse 
OTHER SPECIFICATIONS  
Peak Efficiency97.8 % 

 

Isolation

3.0 kVAC – input to output

1.5 kVAC – input to protective earth

0.5 kVDC – output to protective earth

 

 

Alarms (Red LED)

Low mains shutdown, High and low temperature shutdown, Rectifier Failure, Overvoltage shutdown on output, Fan failure, Low voltage alarm, CAN bus failure 

 

Warnings (Yellow LED)

Rectifier in power derate mode, Remote current limit activated, Input voltage out of range, flashing at overvoltage 
Normal (Green LED)Input and output ok 
MTBF (Telcordia SR-332 Iss.3 method II Case L1)1 900 000 hours 
Operating temperature (5 - 95% RH non-cond.)-40 - 75°C [-40 - 167°F ] 
Max output power de-rates above temp / to45°C [+113°F] / 1800 W 2) 
Storage temperature-40 to +85°C (-40 to +185°F), humidity 0 - 99% RH non-condensing 
Dimensions[WxHxD] / Weight109 x 41.0 x 327mm [4.25 x 1.61 x 13”] / 2.050 kg [4.5lbs] 
DESIGN STANDARDS  
Electrical safetyEN 60950-1:2006+A11:2009+A1:2010+A12:2011+A2:2013, UL 60950-1:2014 
EMC

EN 61000-6-1:2019, -6-2:2019, - 6-3:2007 + A1:2011, - 6-4:2019

ETSI EN 300 386 V.2.1.1, FCC CFR 47 Part 15:2013

 

 

Environment

ETSI EN 300 019: 2-1 (Class 1.2) & 2-2 (Class 2.3) EU 2015/863 (RoHS) & 2012/19/EU (WEEE)

Normal operating conditions as per IEC 62040-5-3:2016 clause 4.2. Other operating conditions as per IEC 62040-5-3:2016 clause 4.3, must be advised

 

 

1) Stand-by / test operation (VOUT < 48VDC) limited for VIN > 230 VAC

2) When input mains voltage is below 210 VRMS temperature derating will start at 40 °C and 1500 W will be available at 75 °C

 

9U hybrid power core with Smartpack2 controller

Hot Products

2-port 100M Ethernet Media Converter IEEE 802.3u 100Base-TX and 100Base-FX Features Support 1 100M ...
2-port 100M Industrial Media Converter Management Card Features Support 2 100M copper ports Input ...
2-port 100M Industrial Media Converter Unmanaged Daughter Card Overview The series adopt industrial ...
2-port 100M Unmanaged Industrial Media Converter Features Support 1 100M fiber port, 1 100M copper ...
3-port 100M Transceiver IP40 Optic Unmanaged Industrial Media Converter Features Support 1 100M ...
3 Port Fast Automatic Flow Control Transceiver Ethernet to Fiber Media Converter Features Support 1 ...